What is going on

Convert the boiler from natural gas to propane, then verify combustion.

Check in this order

  1. Turn off gas and water supply to the boiler.
  2. Remove the front cover by releasing the four latches.
  3. Disconnect the gas inlet pipe from the gas valve at location A (two screws).
  4. Remove the four screws at location B and pull the gas valve off the fan assembly.
  5. Remove the two screws holding the gas orifice and swap in the LP orifice, making sure the packing is seated in the port.
  6. Refit the gas valve outlet adapter and all screws without overtightening.
  7. Inspect the gas valve O-ring and make sure it is in good condition and installed.
  8. Set DIP switch 2 #1 to ON for propane (or OFF for natural gas) and set switches 2 and 3 for altitude.
  9. Turn gas and water back on.
  10. Check CO2 at high fire and low fire, or check offset at low fire, and adjust only if out of range.
  11. Apply the conversion labels next to the rating plate after values are confirmed.

Applies to: NCB-190/060H, NCB-190/080H, NCB-240/110H, NCB-240/130H, NCB-250/150H

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB-H LP gas and high altitude conversion guide, p. 1-2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.