Combustion air requirements for confined and unconfined spaces
What is going on
Sizing rules for combustion air openings based on the appliance Btu input.
Check in this order
- Treat the space as unconfined if its volume is at least 50 cubic feet per 1000 Btu/hr of total appliance input. Tight buildings may still need outside air.
- Treat the space as confined if its volume is less than 50 cubic feet per 1000 Btu/hr. A confined space needs two combustion air openings.
- For indoor air from joining rooms, provide at least 1 sq in of free area per 1000 Btu/hr, minimum 100 sq in per opening.
- For outdoor air through horizontal ducts, provide at least 1 sq in per 2000 Btu/hr of total input (1100 mm² per kW).
- Place the upper opening within 12 in (0.30 m) of the top and the lower opening within 12 in (0.30 m) of the bottom. Keep the openings unobstructed.
- If duct cross section is used, it must be at least equal to the required free area.
- Assume wood louvers give 25% free area and metal louvers or grills give 75%. Do not use openings smaller than 1/4 in.
Applies to: Combustion air supply for all installations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.