Combustion air requirements for confined and unconfined spaces

I-Series Plus

What is going on

Sizing rules for combustion air openings based on the appliance Btu input.

Check in this order

  1. Treat the space as unconfined if its volume is at least 50 cubic feet per 1000 Btu/hr of total appliance input. Tight buildings may still need outside air.
  2. Treat the space as confined if its volume is less than 50 cubic feet per 1000 Btu/hr. A confined space needs two combustion air openings.
  3. For indoor air from joining rooms, provide at least 1 sq in of free area per 1000 Btu/hr, minimum 100 sq in per opening.
  4. For outdoor air through horizontal ducts, provide at least 1 sq in per 2000 Btu/hr of total input (1100 mm² per kW).
  5. Place the upper opening within 12 in (0.30 m) of the top and the lower opening within 12 in (0.30 m) of the bottom. Keep the openings unobstructed.
  6. If duct cross section is used, it must be at least equal to the required free area.
  7. Assume wood louvers give 25% free area and metal louvers or grills give 75%. Do not use openings smaller than 1/4 in.

Applies to: Combustion air supply for all installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.