Viessmann · Boiler troubleshooting
Checking the outdoor temperature sensor
What is going on
Resistance check of the outdoor sensor and cable.
Check in this order
- Disconnect one lead of the sensor cable.
- Measure the sensor resistance at the end of both leads.
- If readings strongly deviate from the curve values, repeat the test and compare with the actual temperature (scan on p. 21).
- Replace the cable or the outdoor temperature sensor depending on the result.
Applies to: Outdoor temperature sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H Installation and Service Instructions, p. 39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.