Checking the outdoor temperature sensor

Vitotronic 200-H

What is going on

Resistance check of the outdoor sensor and cable.

Check in this order

  1. Disconnect one lead of the sensor cable.
  2. Measure the sensor resistance at the end of both leads.
  3. If readings strongly deviate from the curve values, repeat the test and compare with the actual temperature (scan on p. 21).
  4. Replace the cable or the outdoor temperature sensor depending on the result.

Applies to: Outdoor temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H Installation and Service Instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.