Connect the gateway to a Vitotronic 100 / 300 GW2 / 300 GW5B control

Versatronik 501

What is going on

The gateway links to the control through a CAT-5 cable and sends the LON network out on terminals A and B. The control needs its LON communication card fitted.

Check in this order

  1. Confirm the manual for the boiler control is at hand and the LON communication card is installed in the control.
  2. Plug the supplied 3 ft (91 cm) CAT-5 cable with RJ45 connectors into the RJ45 socket on the control's LON card.
  3. Plug the other end into the RJ45 socket inside the Versatronik 501 gateway.
  4. Wire the LON network to gateway terminals A and B.
  5. Connect the plug-in 120VAC power cord to the gateway.

Applies to: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2, Vitotronic 300 GW5B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 501 & 501D LON gateway manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.