Viessmann · Boiler troubleshooting
Connect the gateway to a Vitotronic 100 / 300 GW2 / 300 GW5B control
What is going on
The gateway links to the control through a CAT-5 cable and sends the LON network out on terminals A and B. The control needs its LON communication card fitted.
Check in this order
- Confirm the manual for the boiler control is at hand and the LON communication card is installed in the control.
- Plug the supplied 3 ft (91 cm) CAT-5 cable with RJ45 connectors into the RJ45 socket on the control's LON card.
- Plug the other end into the RJ45 socket inside the Versatronik 501 gateway.
- Wire the LON network to gateway terminals A and B.
- Connect the plug-in 120VAC power cord to the gateway.
Applies to: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2, Vitotronic 300 GW5B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 501 & 501D LON gateway manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.