Viessmann · Boiler troubleshooting
Switch between staged and modulating burner externally
What is going on
A floating contact on plug aVH changes the burner between modulating and two-stage operation.
Check in this order
- Set the burner type to "modulating" in coding 1 (coding "02: 2").
- Connect the floating contact to terminals "1" and "2" on plug aVH.
- Contact open modulating operation.
- Contact closed two-stage operation.
- When the burner type is read, the display still shows "modulating" after the external changeover; this is normal.
Applies to: Boilers with staged/modulating burner
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.