Weil-McLain · Boiler troubleshooting
Check call for heat, limits, connectors and gas pressure
What is going on
Basic checks when the boiler does not fire. Gas pressure limits are from the manual.
Likely causes
- No call for heat at the thermostat
- External limit open
- Loose plug at the control module
- Gas pressure outside range
Check in this order
- Confirm the thermostat is calling for heat and its contacts (including zone controls) are closed.
- Check for 24 VAC between the thermostat wire nuts and ground.
- Make sure all external limit controls are installed and closed, or temporarily jumpered for testing only.
- Check that all connectors to the control module and the originating controls are fully plugged in.
- Gas pressure must not exceed 13 in. w.c. with no flow (lockup) or with the boiler on.
- Minimum gas pressure with gas flowing at high fire: 4 in. w.c. for natural gas (5 in. w.c. for Ultra 299), or 4 in. w.c. for propane.
Applies to: Ultra 80, 105, 155, 230, 299, 399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 116. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.