Rinnai · Boiler troubleshooting

DHW heat exchanger flush with vinegar

I-Series Plus

What is going on

Flush the plate heat exchanger when the LC reminder shows or in hard water areas. Failure to flush can damage the plate heat exchanger. Lime damage is not covered by warranty.

Likely causes

  • Lime scale in the DHW plate heat exchanger

Check in this order

  1. Shut off gas and turn off the DHW and CH buttons on the controller.
  2. Close the shutoff valves on the hot and cold water lines (V3 and V4).
  3. Connect the pump outlet hose H1 to the cold water line at service valve V2.
  4. Connect the drain hose H3 to the hot water line at service valve V1.
  5. Pour four gallons of undiluted food grade white vinegar into a pail.
  6. Place hose H3 and the pump inlet hose H2 into the cleaning solution.
  7. Open service valves V1 and V2.
  8. Remove the front panel and press the SW3 button on the PC board to start the flush mode.
  9. Run the pump and circulate the cleaner, then rinse and disconnect the hoses when complete.

Applies to: All I-Series Plus condensing combi boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 124. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.