Weil-McLain · Boiler troubleshooting

Diaphragm or bladder expansion tank piping (single zone)

CGi Series 5

What is going on

The expansion tank must be sized for the boiler and system water volume and temperature. Place it on the boiler return piping as close to the boiler as possible, before the circulator inlet. Undersized tanks cause relief valve water loss, makeup water and eventual section failure.

Likely causes

  • Undersized expansion tank
  • Tank placed on the wrong side of the circulator

Check in this order

  1. Size the tank for the boiler and system water volume and temperature per the tank maker's instructions.
  2. Install the tank in the boiler return piping as close to the boiler as possible, before the circulator inlet.
  3. Install an automatic air vent as shown in Figure 15.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.