Weil-McLain · Boiler troubleshooting

Annual startup: inspect flame sense assembly

SlimFit Series 2

What is going on

The flame sensor is the shorter rod with a pink ceramic insulator. It mounts on the piping end section.

Likely causes

  • White oxide buildup on the sense rods
  • Damaged gasket or harness
  • Flame sensor in the wrong location

Check in this order

  1. Remove the flame sensor assembly from the piping end section of the heat exchanger.
  2. Remove white oxides from the sense rods with steel wool. If they cannot be cleaned well, replace the assembly.
  3. Reinstall with the gasket in good condition and correctly positioned. Replace the gasket if needed.
  4. Inspect the flame sense harness and connections. Replace as needed.
  5. Confirm the flame sensor is on the piping end, not the burner end.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 90. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.