Annual startup: inspect flame sense assembly
What is going on
The flame sensor is the shorter rod with a pink ceramic insulator. It mounts on the piping end section.
Likely causes
- White oxide buildup on the sense rods
- Damaged gasket or harness
- Flame sensor in the wrong location
Check in this order
- Remove the flame sensor assembly from the piping end section of the heat exchanger.
- Remove white oxides from the sense rods with steel wool. If they cannot be cleaned well, replace the assembly.
- Reinstall with the gasket in good condition and correctly positioned. Replace the gasket if needed.
- Inspect the flame sense harness and connections. Replace as needed.
- Confirm the flame sensor is on the piping end, not the burner end.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.