Viessmann · Boiler troubleshooting

Replace burner tube

Vitocrossal 200 CM2

What is going on

Burner tube and retaining ring with gasket A.

Check in this order

  1. Loosen the retaining clamp and disconnect the combustion air flex hose.
  2. Disconnect the gas line.
  3. Remove the four M12 (19 mm hex) burner door bolts and washers. Disconnect the gas line and plugs as in the burner door procedure.
  4. Remove the four M8 (13 mm hex) burner tube nuts from the burner door.
  5. Remove the burner tube with retaining ring and gasket A.
  6. Rotate the new tube until the studs line up with the holes in the burner door.
  7. Tighten the M8 nuts and M12 door bolts to the torque in the torque table.
  8. Leak test the reconnected gas line.

Applies to: All CM2 models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.