Annual startup and inspection
What is going on
Service technician annual checks. Start with the reported problems and work down the list.
Check in this order
- Investigate reported problems and correct them.
- Inspect the air inlet screen; clean and vacuum if needed. Do not use solvents.
- Clean the base collector and condensate trap, then refill with fresh water.
- Check for water, gas, flue and condensate leaks.
- Check system water chemistry, inhibitor and antifreeze concentration.
- Check the boiler relief valve and expansion tank.
- Verify flue and air lines are sealed and in good condition.
- Check ignition electrode, flame sense rod and ground wiring.
- Check the high gas pressure switch, low gas pressure switch, low water cutoff and operating and high limits.
- Check all wiring and connections.
- Perform startup checkout and performance check beginning on page 85.
- Inspect flame for stable, uniform pattern and check flame signal.
- Clean the heat exchanger if flue temperature is more than 30 °F above return water temperature.
- Check blower speed settings.
Applies to: SVF 1500-3000
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 92-94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.