Annual startup and inspection

SVF Series 1

What is going on

Service technician annual checks. Start with the reported problems and work down the list.

Check in this order

  1. Investigate reported problems and correct them.
  2. Inspect the air inlet screen; clean and vacuum if needed. Do not use solvents.
  3. Clean the base collector and condensate trap, then refill with fresh water.
  4. Check for water, gas, flue and condensate leaks.
  5. Check system water chemistry, inhibitor and antifreeze concentration.
  6. Check the boiler relief valve and expansion tank.
  7. Verify flue and air lines are sealed and in good condition.
  8. Check ignition electrode, flame sense rod and ground wiring.
  9. Check the high gas pressure switch, low gas pressure switch, low water cutoff and operating and high limits.
  10. Check all wiring and connections.
  11. Perform startup checkout and performance check beginning on page 85.
  12. Inspect flame for stable, uniform pattern and check flame signal.
  13. Clean the heat exchanger if flue temperature is more than 30 °F above return water temperature.
  14. Check blower speed settings.

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 92-94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.