Weil-McLain · Boiler troubleshooting
Check thermostat circuits for stray voltage
What is going on
Confirm no voltage is fed back into the control from external devices.
Likely causes
- External thermostat, relay or zone valve wired so it puts voltage on the boiler input terminals
Check in this order
- Mark and disconnect the wires on Input 1, Input 2, Input 3 and Input 4.
- Close each external thermostat, zone valve or relay one at a time.
- Measure voltage from each wire to ground with a voltmeter. There should never be a reading when the external device is closed.
- If voltage is present, correct the external wiring.
- Do not connect the thermostat terminals to 3-wire zone valves.
- Reconnect the wires once the circuit is correct.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 132. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.