Weil-McLain · Boiler troubleshooting

Check thermostat circuits for stray voltage

ECO Tec Series 3

What is going on

Confirm no voltage is fed back into the control from external devices.

Likely causes

  • External thermostat, relay or zone valve wired so it puts voltage on the boiler input terminals

Check in this order

  1. Mark and disconnect the wires on Input 1, Input 2, Input 3 and Input 4.
  2. Close each external thermostat, zone valve or relay one at a time.
  3. Measure voltage from each wire to ground with a voltmeter. There should never be a reading when the external device is closed.
  4. If voltage is present, correct the external wiring.
  5. Do not connect the thermostat terminals to 3-wire zone valves.
  6. Reconnect the wires once the circuit is correct.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 132. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.