Viessmann · Boiler troubleshooting
Dismantle the upper burner section
What is going on
Remove the upper burner section to reach the burner tube, gauze and electrodes. Follow the service preparation steps on page 51 first.
Check in this order
- Close the gas shut-off valve and let the system cool.
- Disconnect the burner gas line.
- Disconnect the connectors from the burner control unit.
- Pull off the ignition electrode connectors.
- Remove 2 screws on the ignition electrode block and lift it off.
- Remove the 6 nuts around the burner mounting plate.
- Remove the upper burner section.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.