Viessmann · Boiler troubleshooting
Direct vent combustion air intake and filter
What is going on
The combustion air intake can be fitted with a field supplied filter. Keep the intake diameter the same through the whole duct. The boiler inlet does not support the weight of duct, filter or housing.
Check in this order
- Use a field supplied filter sized for a 16 x 25 x 1 in high performance furnace filter, such as 3M 1000, 1500 or 1900 series or equivalent.
- Place the filter where there is clearance to inspect and service it.
- Do not reduce the combustion air intake diameter anywhere in the duct.
- Support the air intake ducting, filter and housing so the boiler inlet carries no weight.
- Follow the filter maker's cleaning and replacement schedule.
Applies to: Direct vent installations with combustion air filter
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.