Flow outside Table 5 range
What is going on
Do not size piping for flow above or below the Table 5 range without using a suitable piping strategy. Too little flow causes nuisance limit outages. Too much flow can erode the heat exchanger.
Likely causes
- Flow too low causes nuisance limit outages
- Flow too high causes heat exchanger erosion
Check in this order
- If flow is above Table 5, use primary/secondary piping or add a differential pressure bypass valve in a variable primary system.
- If flow is below Table 5, use primary/secondary piping.
- In variable primary flow, consider a flow switch set at the boiler minimum flow. The variable circulator will raise flow, and the switch will allow the boiler to fire.
Applies to: Boiler loop flow design
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.