Flow outside Table 5 range

SVF 500/600 Series 1

What is going on

Do not size piping for flow above or below the Table 5 range without using a suitable piping strategy. Too little flow causes nuisance limit outages. Too much flow can erode the heat exchanger.

Likely causes

  • Flow too low causes nuisance limit outages
  • Flow too high causes heat exchanger erosion

Check in this order

  1. If flow is above Table 5, use primary/secondary piping or add a differential pressure bypass valve in a variable primary system.
  2. If flow is below Table 5, use primary/secondary piping.
  3. In variable primary flow, consider a flow switch set at the boiler minimum flow. The variable circulator will raise flow, and the switch will allow the boiler to fire.

Applies to: Boiler loop flow design

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.