Weil-McLain · Boiler troubleshooting
Diaphragm or bladder expansion tank piping and pressure
What is going on
Size the tank for boiler and system water volume and temperature. Undersized tanks lose water through the relief valve and add make-up water, which can eventually fail the boiler.
Likely causes
- Undersized expansion tank
- Tank air charge not matched to cold fill pressure
Check in this order
- Locate the air separator and expansion tank as shown on pages 60 to 62.
- Always locate the cold-water fill connection at the expansion tank.
- Calculate cold fill pressure and set the tank air charge to the same value, checking with the tank removed from the system.
- Confirm operating pressure after heat expansion stays at or below 24 PSIG.
- Install an automatic air vent on top of the air separator per the separator instructions.
- Add extra tanks by tying them into system tees if more expansion volume is needed.
Applies to: Diaphragm or bladder type expansion tank (Figure 66)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.