Weil-McLain · Boiler troubleshooting
Pilot lights, main valve will not come on (pilot and gas valve check)
What is going on
Chart 5 for steam and water EG/PEG boilers, with or without vent damper. Confirms pilot gas flow, spark gap and gas valve operation.
Likely causes
- Loose pilot valve connections
- Manual hand valve closed
- Inlet gas pressure out of range
- Spark gap incorrect or not in pilot gas stream
- Gas cock off or pilot line kinked or blocked
- Clogged pilot orifice
- Faulty gas valve
Check in this order
- Block any draft around the boiler.
- Check that the pilot valve connections are correct and securely fastened.
- Open the manual hand valve.
- Check that inlet gas pressure is at least 5.0 in. w.c. and not more than 14.0 in. w.c. If not, contact the gas supplier to correct pressure.
- Check that the spark gap is 0.125 in. and located in the pilot gas stream. If not, replace the pilot assembly.
- Check for gas at the pilot burner assembly: remove the wire to MV on the ignition control, then use a match taped to a long screwdriver or pilot lighter rod to light the pilot manually.
- If the pilot lights, reconnect securely to terminals PV and MV/PV on the ignition control and open the manual hand valve.
- If the pilot does not light, check that the gas cock is in the ON position and the pilot line is not kinked or obstructed, and check for a clean pilot orifice.
- If the orifice is clean and gas flows, replace the gas valve.
Applies to: EG and PEG Series 7 steam and water boilers, natural gas
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG/PEG Series 7 boiler manual, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.