Shut down the boiler for service
What is going on
Isolate power and gas before opening the boiler.
Check in this order
- Switch off the main circuit breaker or power supply and prevent unauthorized reconnection.
- Remove the boiler front cover.
- Unplug burner cables fA and lÖ from the burner control and route them out of the burner casing.
- Close the gas shut-off valve.
- Remove the gas supply pipe.
- Undo the four screws on the boiler door and open the door.
- Do not put tools or objects into the combustion chamber.
Applies to: Vitocrossal 200 CM2 186 to 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.