Viessmann · Boiler troubleshooting

Check the fixed high limit via the TUV button

Vitotronic 100

What is going on

The adjustable high limit R is bridged for this check. A minimum supply is needed during the test. Recirculated water should be at least 10% of the rated load amount, and heat use should be reduced as far as possible. The burner runs until the fixed high limit cuts it off at the safety temperature.

Check in this order

  1. Hold the TUV button continuously pressed during the check.
  2. Run the burner until boiler water reaches the safety temperature and the fixed high limit operates.
  3. Release the TUV button once the burner has switched off.
  4. Wait until boiler water has dropped 15 to 20 °C (27 to 36 °F) below the selected safety temperature.
  5. Reset the fixed high limit by pressing the E button.

Applies to: Vitotronic 100 GC1 fixed high limit check

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.