Annual startup: check ignition cable and ground wiring
What is going on
Check ignition cable resistance and ground continuity from the ignitor to the ground terminal strip.
Likely causes
- Ignition cable out of range
- Poor or broken ground wire
- Damaged wiring
Check in this order
- Measure the ignition cable resistance. A good cable reads 900 to 1000 ohms. Replace it if outside that range.
- Inspect the ground wire from the ignition electrode to the ground terminal strip.
- Check that all wiring is in good condition and firmly attached.
- Check ground continuity with a continuity meter.
- Replace ground wires that do not test satisfactorily.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.