Weil-McLain · Boiler troubleshooting

Expansion tank and make-up water

SVF 500/600 Series 1

What is going on

Size the expansion tank for the boiler and system water volume and temperature (boiler water content is in Table 27, page 142). An undersized tank causes relief valve water loss and excess make-up water, which can eventually fail the boiler. Connect the expansion tank to the air separator only if the separator is on the pump suction side. Put the system fill connection at the same point as the expansion tank connection.

Likely causes

  • Undersized expansion tank
  • Excess make-up water added through fill valve

Check in this order

  1. Size the tank for boiler and system water volume and temperature.
  2. Connect the tank to the air separator only if the separator is on the pump suction side.
  3. Install the system fill connection at the same point as the expansion tank connection.
  4. With a diaphragm or bladder tank, install an automatic air vent on top of the air separator.
  5. With a diaphragm or bladder tank and boiler above main piping, install an automatic air vent at the top of the outgoing boiler piping.
  6. Charge a diaphragm or bladder tank to system fill pressure before connecting it.
  7. With a closed-type tank, do not use automatic air vents. Remove any vent on the heat exchanger before operation.
  8. With a closed-type tank, pitch horizontal piping toward the tank at 1 in per 5 ft and connect with at least 3/4 in piping.

Applies to: System expansion and fill

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, pp. 22-23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.