Viessmann · Boiler troubleshooting
Replace the rotary damper and servomotor
What is going on
Remove and refit the rotary damper, air pressure switch and servomotor as one assembly. The damper must be fully open when the burner is off and during operation.
Likely causes
- Damper not fully open during operation
- Incorrect servomotor adjustment
Check in this order
- Disconnect the servomotor connector.
- Remove the 4 screws holding the rotary damper and its retaining bracket (13 lb.in / 1.5 Nm on refit) and lift out the damper with the bracket.
- Remove the 2 screws on the servomotor shaft (3 lb.ft / 4 Nm on refit) and take off the servomotor.
- Release the articulated rod on the rotary damper with an open-ended wrench.
- Fit the new damper, air pressure switch and servomotor in reverse order.
- If the damper is not fully open, adjust it with the articulated rod and check the servomotor settings.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.