Viessmann · Boiler troubleshooting

Clean the burner fan and Venturi mixing tube

Vitocrossal 300 CA3B Dual Fuel

What is going on

Clean the fan and check the gasket and gas connections on reassembly.

Likely causes

  • Dirty fan housing or impeller
  • Damaged fan housing gasket

Check in this order

  1. Close the central gas shut-off valve.
  2. Disconnect the Venturi mixing tube from the fan.
  3. Detach the Venturi mixing tube with the combination gas valve and gas connector pipe; detach connector pipes if fitted.
  4. Detach connector pipes a-Ö and a-ÖA from the fan and remove the fan.
  5. Clean the fan housing and impeller with compressed air.
  6. Vacuum the burner tube from inside and out if needed.
  7. Reassemble in reverse order and fit the gasket between the fan housing and burner plate in the correct position.
  8. Check for gas leaks at the screws and the fan housing gasket.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.