Viessmann · Boiler troubleshooting

Replace rotary damper and servomotor

Vitocrossal 300 CA3B

What is going on

For CA3B 3.5 to 6.0, the rotary damper must be fully open when the burner is off and while it runs. An incompletely open damper can cause malfunction or show incorrect servomotor adjustment.

Likely causes

  • Incomplete damper opening
  • Incorrect servomotor adjustment

Check in this order

  1. Disconnect the servomotor connector.
  2. Undo the 4 screws on the damper retaining bracket (torque 13 lb.in / 1.5 Nm) and remove the damper with the bracket.
  3. Undo the 2 screws on the servomotor axis (torque 3 lb.ft / 4 Nm) and remove the servomotor.
  4. Release the articulated rod on the damper with an open-ended wrench.
  5. Install the new damper, air pressure switch and servomotor in reverse order.
  6. If needed, adjust the damper with the articulated rod so it is fully open. Use the servomotor settings in the service instructions.

Applies to: CA3B Series 2.5 to 6.0, rotary damper for 3.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.