Weil-McLain · Boiler troubleshooting
WMZV zone valve controller plus boiler-controlled DHW
What is going on
DHW is piped directly to the boiler. The zone controller calls for heat on INPUT 2, and the system circulator on OUTPUT 2 runs whenever the zone controller calls. DHW is on INPUT 1 and PRIORITY 1, with the DHW circulator on OUTPUT 1.
Check in this order
- Wire the zone controller call for heat (X-X) to INPUT 2 and keep INPUT 2 on PRIORITY 2.
- Wire the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
- Wire the DHW circulator to OUTPUT 1.
- Wire the system circulator to OUTPUT 2.
- Set the heating system type in PRIORITY 2 as required.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.