Weil-McLain · Boiler troubleshooting

WMZV zone valve controller plus boiler-controlled DHW

SlimFit Series 2

What is going on

DHW is piped directly to the boiler. The zone controller calls for heat on INPUT 2, and the system circulator on OUTPUT 2 runs whenever the zone controller calls. DHW is on INPUT 1 and PRIORITY 1, with the DHW circulator on OUTPUT 1.

Check in this order

  1. Wire the zone controller call for heat (X-X) to INPUT 2 and keep INPUT 2 on PRIORITY 2.
  2. Wire the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
  3. Wire the DHW circulator to OUTPUT 1.
  4. Wire the system circulator to OUTPUT 2.
  5. Set the heating system type in PRIORITY 2 as required.

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.