Viessmann · Boiler troubleshooting

Power supply connection to the control

Vitotronic 200Vitotronic 300-K

What is going on

The control needs 120 VAC, single phase, 60 Hz, with grounding. Overcurrent protection of at least 6 A and a 2-pole disconnect must be on the supply.

Check in this order

  1. Confirm the supply has a 2-pole disconnect and at least 6 A overcurrent protection per local code.
  2. Connect line to terminal 11, neutral to N and ground to G on the DIN rail in the junction box.
  3. Check that L, N and G are not swapped.
  4. Verify the control is grounded before power-up.

Applies to: Vitotronic 300-K power supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.