Viessmann · Boiler troubleshooting
Power supply connection to the control
What is going on
The control needs 120 VAC, single phase, 60 Hz, with grounding. Overcurrent protection of at least 6 A and a 2-pole disconnect must be on the supply.
Check in this order
- Confirm the supply has a 2-pole disconnect and at least 6 A overcurrent protection per local code.
- Connect line to terminal 11, neutral to N and ground to G on the DIN rail in the junction box.
- Check that L, N and G are not swapped.
- Verify the control is grounded before power-up.
Applies to: Vitotronic 300-K power supply
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.