Weil-McLain · Boiler troubleshooting
Outdoor reset operation
What is going on
Outdoor reset adjusts supply target temperature to outdoor temperature. Max target is for design maximum heat loss. Min target is the supply temperature used when outdoor temperature is above the outdoor temp for min target. Outdoor temp for max target should equal the site design outdoor temperature.
Check in this order
- Set the desired space heating zone temperatures.
- Set MAX TARGET TEMP to the design supply water temperature (typically 180°F for finned tube baseboard on new installs).
- Set MIN TARGET TEMP to the lowest acceptable supply temperature; do not set it below the outdoor temp for min target unless heating performance loss is acceptable.
- Set OUTDOOR TEMP FOR MIN TARGET and OUTDOOR TEMP FOR MAX TARGET to match the site (factory defaults are 70°F and 0°F).
- Make these settings in the priority menu for the system.
Applies to: Space heating priorities with outdoor sensor
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Advanced Manual, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.