Viessmann · Boiler troubleshooting

Check boiler temperature sensor and fixed high limit

Vitodens 200-W B2HA

What is going on

Boiler water temperature sensor and fixed high limit. Drain the boiler before replacing the sensor because the sensor sits in hot heating water.

Likely causes

  • Sensor resistance deviates severely from the curve

Check in this order

  1. Drain the boiler.
  2. Remove the lead from the boiler water temperature sensor or fixed high limit and check the resistance.
  3. Compare the value with the curve (NTC 10 kΩ).
  4. Replace the sensor if the deviation is severe.

Applies to: Vitodens 200-W B2HA

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA service instructions, p. 85. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.