Weil-McLain · Boiler troubleshooting
Tankless coil water goes cold or stays lukewarm (steam boiler)
What is going on
Domestic hot water from the tankless coil is hot then turns cold, or never gets fully hot.
Likely causes
- Mineral scale inside the coil
- Stop-leak added to the boiler is coating the outside of the coil
- Mixing valve set wrong
- Hot water flow too high for the coil
- Tankless control set too low or differential too wide
Check in this order
- Check the mixing valve setting.
- Install a flow check valve sized to the coil rating if flow is too high.
- Raise the tankless control setting and lower its differential.
- Scaled coil de-lime or replace it.
- If stop-leak was added, pull and clean the coil and drain and flush the boiler.
Applies to: SGO-3 to SGO-9 oil-fired steam boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.