Weil-McLain · Boiler troubleshooting

Tankless coil water goes cold or stays lukewarm (steam boiler)

Weil-McLain SGO Series 4

What is going on

Domestic hot water from the tankless coil is hot then turns cold, or never gets fully hot.

Likely causes

  • Mineral scale inside the coil
  • Stop-leak added to the boiler is coating the outside of the coil
  • Mixing valve set wrong
  • Hot water flow too high for the coil
  • Tankless control set too low or differential too wide

Check in this order

  1. Check the mixing valve setting.
  2. Install a flow check valve sized to the coil rating if flow is too high.
  3. Raise the tankless control setting and lower its differential.
  4. Scaled coil de-lime or replace it.
  5. If stop-leak was added, pull and clean the coil and drain and flush the boiler.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.