Rinnai · Boiler troubleshooting

Hot water works, no central heating

What is going on

Rinnai E50CRN, E75CRN, E75CRP, E110CRN, E110CRP. Hot water fine, no space heating. Check the call for heat first, then the diverter.

Likely causes

  • CH program key off
  • On/off room thermostat sending no call
  • RS100 with outdoor sensor: outdoor temperature above the Eco setting (default 70 F)
  • Three-way valve not going to the CH position

Check in this order

  1. Switch central heating on at the control.
  2. Check the room thermostat is calling.
  3. With an RS100, check INFO step 7 and the timer and room temperature settings.
  4. Check three-way valve wiring, power off. Replace the valve motor if needed.
  5. Confirm radiators warm up after a call

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.