Viessmann · Boiler troubleshooting

LON wiring of the gateway to a Vitotronic 300 control

Versatronik 581 / 581D

What is going on

Connect the gateway to the boiler control over LON and supply power. The manual gives 24VAC and 120VAC power options. Use the wiring diagram for the specific control.

Check in this order

  1. Turn off power to the control and any damper or blower before working on it.
  2. Confirm the LON communication card is installed in the boiler control (required for Vitotronic 300-K MW2C and B2HA boilers).
  3. Plug the supplied CAT-5 cable (RJ45) into the RJ45 socket on the control and the other end into the RJ45 socket inside the gateway.
  4. Wire the field LON 2-wire connection to gateway terminals A and B.
  5. Power the gateway field-supplied 24VAC supply, or the plug-in power cord for 120VAC gateways.
  6. Use the wiring diagram for the specific control model to confirm connections before restoring power.

Applies to: Vitotronic 300 GW5B, GW6B (single and cascade), 300-K MW2C (B2HA)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 581 LON gateway manual, p. 8-12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.