Weil-McLain · Boiler troubleshooting
Automatic air vent check
What is going on
Applies only to systems with diaphragm-type expansion tanks. Automatic air vents must not be used with other tank types.
Likely causes
- Air vent stuck or leaking
Check in this order
- Remove the cap from the automatic air vent.
- Depress the valve pin slightly with a screwdriver tip and check that the vent operates freely without leaking. Water from the vent may be very hot.
- Reinstall cap A, twisting it all the way on.
- Loosen cap A one turn so the vent can operate.
- Have the vent replaced if it does not operate correctly.
Applies to: 110/155/220/299/300/399 Series 2 with diaphragm expansion tank
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Evergreen Series 2 user's information manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.