Viessmann · Boiler troubleshooting

Disconnecting burner wiring

Vitocrossal 300 CA3B Dual Fuel

What is going on

Disconnect the burner harness before removing the burner from its casing. Plug labels on the printed page are partly garbled.

Check in this order

  1. Close the gas shut-off valve.
  2. Switch off the main circuit breaker or power supply and prevent unauthorized reconnection.
  3. Remove the boiler left side panels.
  4. Disconnect the power cable plug.
  5. Disconnect the burner cables from the burner control unit, including the KM-BUS plug, then pull the burner out of the casing.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel CA3B service instructions, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.