Combustion air openings to the boiler room
What is going on
A direct vent boiler alone in a room needs no ventilation openings if the room keeps the minimum service clearances from Figure 2. If it does not, use the direct vent openings on page 38. A direct exhaust boiler takes combustion air from the room, so openings must be sized for the boiler and all other appliances in that room. When other appliances share a direct vent room, size the openings for those appliances only. The control can run a combustion air damper through the Aux/Pump output.
Check in this order
- Confirm whether the installation is direct vent or direct exhaust.
- For direct vent, check the room keeps the Figure 2 service clearances; if not, size openings per page 38.
- For direct exhaust, size openings for ALL appliances in the room, including the SVF boiler.
- If a combustion air damper is used, wire it through the Aux/Pump output in the controls section.
Applies to: All SVF 1500-3000 installations
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.