Remove the heat exchanger cover plate and burner
What is going on
Open the heat exchanger for access. Disconnect power and close the gas supply before you start.
Check in this order
- Close the external manual gas valve.
- Disconnect all power to the boiler.
- Let the boiler cool if it has been operating.
- Use a 13 mm wrench or socket to remove the nuts that hold the heat exchanger cover plate.
- Remove the burner using the burner removal procedure. Disconnect wire harnesses as needed to move the mixing tube and blower assembly aside.
- Label all wires before disconnecting them.
- Remove the flue inspection cover.
Applies to: SlimFit SF-550 and SF-750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 106. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.