Viessmann · Boiler troubleshooting
Mixing valve extension kit communication lost (emergency mode)
What is going on
If the PlusBus link to a mixing valve extension kit fails, the affected heating circuit switches to emergency mode after 20 minutes. Until then, the extension outputs hold their last state.
Likely causes
- Communication break on PlusBus to the mixing valve extension kit
Check in this order
- Check the PlusBus wiring between the HMU and the mixing valve extension kit.
- Check that the extension kit has power.
- Clear the fault once the link is restored and confirm the heating circuit leaves emergency mode.
- Note that the mixing valve is closed and the circuit pump runs while in emergency mode.
Applies to: Heating circuits with mixing valve extension kit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.