Viessmann · Boiler troubleshooting

Mixing valve extension kit communication lost (emergency mode)

Vitocrossal 200 CI2

What is going on

If the PlusBus link to a mixing valve extension kit fails, the affected heating circuit switches to emergency mode after 20 minutes. Until then, the extension outputs hold their last state.

Likely causes

  • Communication break on PlusBus to the mixing valve extension kit

Check in this order

  1. Check the PlusBus wiring between the HMU and the mixing valve extension kit.
  2. Check that the extension kit has power.
  3. Clear the fault once the link is restored and confirm the heating circuit leaves emergency mode.
  4. Note that the mixing valve is closed and the circuit pump runs while in emergency mode.

Applies to: Heating circuits with mixing valve extension kit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.