Unpacking and rolling the boiler off the skid

Vitocrossal 200 CI2

What is going on

The boiler is on a wooden pallet with wheels for placement. It can be lifted by crane only while still packed on the skid. Ramp length depends on model. The boiler can cause serious injury if it tips, so at least two people are needed.

Check in this order

  1. Remove packaging and unscrew the transport brackets.
  2. Position the ramp at the front of the boiler with enough room to unload it from the skid. Use a 50 in. (1270 mm) ramp for models 399 to 1000, and a 75 in. (1900 mm) ramp for models 1500 and 2000.
  3. Using an open-end wrench, wind the adjustable feet in.
  4. Roll the boiler off the pallet in a straight line with at least two people.
  5. Do not push on the jacketing to remove the boiler from the skid.

Applies to: Vitocrossal 200 CI2 399 to 2000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 installation instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.