Viessmann · Boiler troubleshooting
Fixed high limit test, simulation #2 (jumpered flow switch, boiler valve closed)
What is going on
Alternate high limit test. Boiler valve closed and flow switch jumpered so the boiler overheats until the fixed high limit trips.
Check in this order
- Close the boiler valve.
- Jumper across the flow switch.
- Run the boiler at high fire. Coding card set to maximum on B2TB models (coding address 06).
- Let the boiler temperature keep rising until the fixed high limit trips.
- Slowly open the boiler valve to cool the boiler down safely.
Applies to: Vitodens 200-W B2HA 45, 60 (CSD-1 high limit field test)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.