Viessmann · Boiler troubleshooting
Check mixing valve extension kit rotation and direction
What is going on
The boiler runs a self-test after power-up in which the mixing valve opens and closes again. The flow sensor must read higher when the valve is opened. If the temperature drops, the motor is turning the wrong way or the valve set is fitted incorrectly.
Likely causes
- Motor turning in wrong direction
- Mixing valve set incorrectly fitted
Check in this order
- After the self-test, set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, remove the upper casing cover of the extension kit.
- At plug gS, swap the cores at terminals '|' and '~'.
- Refit the casing cover.
Applies to: Extension kit for heating circuit with mixing valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 85. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.