Viessmann · Boiler troubleshooting

Check sensors and actuators

Versatronik 200

What is going on

General check of the sensor and actuator wiring when the system malfunctions.

Likely causes

  • Controller or control components are wired incorrectly.
  • Mixing valve motor direction is wrong.

Check in this order

  1. Check the controller and control components are wired correctly.
  2. Check every sensor in the Sensor test level; all connected sensors must show plausible values.
  3. Check every actuator in the Relay test level, including mixing valve direction of rotation and pump switching.

Applies to: Versatronik 200 system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 166. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.