Viessmann · Boiler troubleshooting
Vertical vent termination location and roof passage
What is going on
Vent termination must be kept out of reach of snow and must not be blocked by drifting snow. Special positive pressure vent systems through a roof need extra height. Other appliance flues must not share the vent.
Check in this order
- Place the vent termination at least 12 in. (305 mm) above the anticipated snow level and where snow cannot block it.
- On a roof pass-through with special positive pressure venting, extend the vent at least 18 in. (450 mm) above the highest roof penetration point and any obstruction within 18 in. (450 mm) horizontally.
- Do not route the special vent into, through or within any other vent such as an existing masonry or factory-built chimney.
- Use a masonry chimney flue only if no other appliance is vented into it.
- On a flat roof, install the vent in line with local regulations, CAN/CSA-B149.1 or .2, or ANSI Z223.1 / NFPA 54.
- Support the venting system with supports rated for the weight and design of the materials, using anchor plates, wall supports, roof supports, floor supports or hangers. Brace it as needed with wall bands, guy wire bands or roof braces. The boiler does not carry the vent weight.
Applies to: All vertical and roof vent installations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.