Viessmann · Boiler troubleshooting
Fill the condensate trap with water
What is going on
Prime the siphon before startup so flue gases cannot escape through the drain.
Check in this order
- Unscrew union nut F and pull condensate trap C down off the connection.
- Fill condensate trap C with water.
- Reinstall the trap and tighten union nut F.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.