Navien · Boiler troubleshooting
Closed loop system requirements and air removal
What is going on
The boiler is only for pressurized closed loop heating systems that are free of air and debris. Open systems are not approved.
Likely causes
- Air trapped in the system
- Low water level or blocked air vent cap
- Leaks causing repeated makeup water
Check in this order
- Do not use the boiler on open systems or for direct heating of potable water.
- Confirm the system is closed and pressurized, with water pressure of 12 to 30 psi at the boiler outlet.
- Install air bleed devices of the right size at strategic points across the heating system, as shown in the piping examples.
- Purge all air during commissioning.
- Check the water level is correct and the air vent cap is not blocked.
- Repair any leak immediately to avoid adding makeup water, since fresh water brings air and minerals that can fail the heat exchanger.
Applies to: NCB700 space heating system
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation manual, p. 183-184. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.