Annual service checks by heating technician

Vitocrossal 300 CA3B

What is going on

Annual service and testing. Owner ensures the service is done at least yearly and corrects deficiencies right away.

Check in this order

  1. Test safety high limits.
  2. Test and establish correct chemical makeup of system water.
  3. Check flue pipe condition, chimney connection and chimney.
  4. Check pressure relief valve and system pressure, and verify operation.
  5. Check heating pipe joints, valves and air vents; correct leaks immediately and find the cause of any defect.
  6. Check combustion air supply and ventilation to the boiler and mechanical room.
  7. Test high limits by lowering settings, then switching burners on and off to verify function.
  8. Test low water cutoff per manufacturer instructions.
  9. Check maintenance or lubrication needs for circulation pumps per manufacturer instructions.
  10. Check gas piping, unions, gas valve and manifold for gas-tight connections.
  11. Check proper burner ignition.
  12. Perform combustion test.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B service instructions, p. 163. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.