Weil-McLain · Boiler troubleshooting

Water chiller piping (zone valves, primary/secondary)

SlimFit Series 3

What is going on

The chiller is piped in parallel with the boiler and must be kept from the boiler loop.

Check in this order

  1. Pipe the chiller in parallel with the boiler.
  2. Install valves so chilled medium cannot enter the boiler.
  3. If the heating coils sit in air handlers exposed to refrigerated air, use flow control valves or another automatic method to stop gravity circulation during cooling.
  4. Use only antifreeze listed by WM Technologies for this boiler. Consider antifreeze effects on circulator sizing and DHW performance.
  5. If local code requires, use a double-wall DHW heat exchanger.
  6. Optional circulator zoning needs a separate circulator for the chilled loop and one per zone.
  7. Provide the expansion tank and flow/check valve as in the other layouts.

Applies to: SF-550 and SF-750

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual 550-100-559/0725, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.