Viessmann · Boiler troubleshooting

Checking and correcting the rotation direction of the mixing valve motor

Vitocrossal 300 CU3A

What is going on

The boiler runs a self-test at power-up that opens and closes the mixing valve. If the supply sensor temperature drops when the valve should be opening, the motor is turning the wrong way or the valve set is fitted incorrectly.

Likely causes

  • Motor turning in the wrong direction
  • Mixing valve set incorrectly fitted

Check in this order

  1. Switch on the boiler and let the self-test run.
  2. During the self-test, set the mixing valve manually to Open.
  3. Check that the supply temperature sensor reads a higher temperature.
  4. If the temperature drops, disconnect main power before opening the boiler.
  5. Remove the upper casing cover of the extension kit.
  6. At plug gS, swap the cores at terminals in the marked positions.
  7. Refit the casing cover.

Applies to: Extension kit mixing valve motor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 97. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.