Viessmann · Boiler troubleshooting
External 0-10 V signal connection for boiler water setpoint
What is going on
A 0-10 V signal from an external controller sets the maximum boiler water temperature. Example from the manual: 8 VDC equals 176 ºF (80 ºC). The full voltage-to-temperature chart is not on these pages.
Check in this order
- Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
- Check the polarity.
- Use the chart in the manual to find the required signal for the desired maximum water temperature.
Applies to: Vitodens 200-W B2HA 80-100, 285-352 with EA1 module
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.