Viessmann · Boiler troubleshooting
Check the flue gas flapper
What is going on
Inspect the flapper behind the fan.
Check in this order
- Undo three screws and remove fan A.
- Remove the flue gas flapper B.
- Check the flapper and gasket for dirt and damage. Replace as needed.
- Refit the flapper and the fan with three screws. Torque 2.2 lb.ft. (3.0 Nm).
Applies to: Vitodens 200-W B2HA 19, 28, 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.