Check condensate drain and neutralizing unit
What is going on
If condensate does not drain, it builds up in the boiler and the burner shuts down with a fault message.
Likely causes
- Blocked or contaminated condensate drain
- Exhausted neutralizing granulate
Check in this order
- Check condensate pH with a pH strip. Replace granulate if pH is below 6.5.
- If contaminated, rinse the neutralizing unit with tap water.
- Add granulate up to the minimum level marked in red.
- Pull off the drain hose and clean the drain hose and pipe at least once a year.
- Flush lower part D of siphon B, refill with water and reassemble.
- Reconnect the neutralizing hose to the siphon.
- Add water to the combustion chamber and confirm it drains without back pressure. Clean the drain again if needed.
Applies to: Vitocrossal 200 CM2 186 to 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.