Viessmann · Boiler troubleshooting

Check condensate drain and neutralizing unit

Vitocrossal 200 CM2

What is going on

If condensate does not drain, it builds up in the boiler and the burner shuts down with a fault message.

Likely causes

  • Blocked or contaminated condensate drain
  • Exhausted neutralizing granulate

Check in this order

  1. Check condensate pH with a pH strip. Replace granulate if pH is below 6.5.
  2. If contaminated, rinse the neutralizing unit with tap water.
  3. Add granulate up to the minimum level marked in red.
  4. Pull off the drain hose and clean the drain hose and pipe at least once a year.
  5. Flush lower part D of siphon B, refill with water and reassemble.
  6. Reconnect the neutralizing hose to the siphon.
  7. Add water to the combustion chamber and confirm it drains without back pressure. Clean the drain again if needed.

Applies to: Vitocrossal 200 CM2 186 to 311

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.