Viessmann · Boiler troubleshooting

Filling the condensate trap

Vitocrossal 300 CA3B

What is going on

Fill the siphon before start-up so flue gas cannot escape through the trap.

Check in this order

  1. Remove siphon cup A and fill it with water.
  2. Check that condensate drains freely.
  3. Refit siphon cup A.
  4. Do not let the hose to the condensate or neutralizing system sag. Support it where needed.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B service instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.